Spandrel:
0.750 to 0.900W/m²·K/0.132 to 0.159Btu/ft²·°F·hr
#object[Error Error: No matching clause: ]
#object[Error Error: No matching clause: ]
#object[Error Error: No matching clause: ]
Transmittance ranges: | |
---|---|
Clear Wall | 0.161 to 0.383W/m²·K/0.028 to 0.068Btu/ft²·°F·hr |
Construction types | Concrete and Mass Masonry |
The following parameters are constant across the scenarios for this detail:
406 mm | horizontal spacing of framing and secondary attachments |
---|---|
Air | interior/cavity insulation |
sub-reference | vertical spacing of secondary elements | exterior insulation | clear field effective R-value | clear field transmittance | |
---|---|---|---|---|---|
A | 610 mm | RSI 2.27 | RSI 2.61 | 0.383 W/m²·K | |
B | 610 mm | RSI 3.03 | RSI 3.28 | 0.305 W/m²·K | |
C | 610 mm | RSI 3.79 | RSI 3.94 | 0.254 W/m²·K | |
D | 610 mm | RSI 4.54 | RSI 4.60 | 0.217 W/m²·K | |
E | 610 mm | RSI 5.30 | RSI 5.24 | 0.191 W/m²·K | |
F | 610 mm | RSI 6.06 | RSI 5.90 | 0.169 W/m²·K | |
G | 914 mm | RSI 2.27 | RSI 2.65 | 0.378 W/m²·K | |
H | 914 mm | RSI 3.03 | RSI 3.34 | 0.299 W/m²·K | |
I | 914 mm | RSI 3.79 | RSI 4.04 | 0.248 W/m²·K | |
J | 914 mm | RSI 4.54 | RSI 4.73 | 0.211 W/m²·K | |
K | 914 mm | RSI 5.30 | RSI 5.40 | 0.185 W/m²·K | |
L | 914 mm | RSI 6.06 | RSI 6.09 | 0.164 W/m²·K | |
M | 1 219 mm | RSI 2.27 | RSI 2.67 | 0.375 W/m²·K | |
N | 1 219 mm | RSI 3.03 | RSI 3.38 | 0.296 W/m²·K | |
O | 1 219 mm | RSI 3.79 | RSI 4.09 | 0.244 W/m²·K | |
P | 1 219 mm | RSI 4.54 | RSI 4.80 | 0.208 W/m²·K | |
Q | 1 219 mm | RSI 5.30 | RSI 5.49 | 0.182 W/m²·K | |
R | 1 219 mm | RSI 6.06 | RSI 6.20 | 0.161 W/m²·K |